I want to know the number of input/output points for the SA350 multipurpose controller.
Yakumo Suishin
SA350 (Information Section) and SA350-IF (Input/Output Section)
The multi-purpose monitoring controller has an information section and an input/output section, each with an input/output interface.
SA350(Information Section)
SA350-IF(Input/Output Section)
Digital Input
SA350(Information Section)
- Non-voltage contact input, power failure compensation input 4 points
- Power failure (power abnormality), surge arrester failure, door open/close signal, spare input (4 points)
SA350-IF(Input/Output Section)
- 16 non-voltage contact inputs
- Switchable to 4 device operation inputs, 2 pulse integration inputs
Digital Output
SA350
-
4 a-contact outputs that can turn AC250V/0.5A on/off
- (Fan, heater, water level output 2 points)
SA350-IF
- 4 a-contact outputs that can turn AC250V/0.5A on/off (remote control output)
Analog Input
SA350-IF (Input/Output Section): 5 points
-
2 two-wire water level gauge inputs
- (Can be switched to 4-20mA by changing wiring. With 10-point broken line approximation function. With analog pulse conversion/integration function)
- 1 0-5V voltage input
- 2 operating current inputs (100A/300A range switchable by setting)